The vendor tool gives the number. You have to know if it is right.
Final sizing of control valves, on/off valves and flow meters happens in vendor software (E+H Applicator, Fisher Specification Manager and others). They hold the tested coefficients. You still decide what goes in and whether what comes out makes sense: Will it cavitate? Is it too loud? Is the pressure drop worth it? Will the meter read at minimum flow? This app teaches that judgment. Every answer explains itself; wrong answers come back until they stick.
What happens in a sizing run, in 8 steps
The same chain for a control valve, an on/off valve or a meter. The Toolbox labs let you run steps 3–7 yourself.
- Collect the casesMinimum, normal, maximum flow; P1, P2, T for each; start-up and upsets.
- Collect the fluidDensity, viscosity, vapour and critical pressure; for gases M, γ, Z.
- Required capacityCv or Kv per case; meter velocity and Reynolds per size.
- LimitsChoked flow, cavitation (σ), flashing; gas choking at Fγ·xT.
- Pick size and trimTravel 10–90% across cases; meter in its velocity window.
- Noise and velocity85 dBA at 1 m, outlet Mach, trim exit energy.
- Actuator and shutoffTorque or thrust at minimum air, fail position, leakage class, stroke time.
- Review the reportRead every case, question every warning, then fill the data sheet.
Mastery by domain
Line = 80% goal. Click a domain to practice it.How to use this
- Study a domain's notes. Start with Fluids, then Cv sizing, Cavitation and Flow meters.
- Practice daily. Missed questions return the same day; known ones space out to 35 days.
- Drill the calculations: Kv/Cv, choked ΔP, σ, travel, DP scaling, surge, actuator torque.
- Labs: size a valve across three cases, watch authority bend a characteristic, screen flow meters, and check an on/off valve for surge.
For learning only, not for design. Valve coefficients (FL, xT, rated Cv) are typical values; real ones come from the vendor for the exact trim. Equations follow IEC 60534-2-1 without piping-geometry or viscosity corrections. Progress stays in this browser.
Keys: 1–4 to answer, Enter for next.
Have a calculator ready. Keys: 1–4, Enter.
Skills check
A timed mix of every domain, about a quarter calculations. No feedback until you submit. You can flag questions and jump around.
The goal is 80%, this app's own bar for "I can judge a vendor sizing report".
History
1 · Control valve lab: three cases, one valve
| Case | Flow | P1 bar(a) | P2 bar(a) | T °C |
|---|---|---|---|---|
| Min | ||||
| Normal | ||||
| Max |